Categories:

MCH-600XF-01 Rotary Desiccant Dehumidifier

  • Dehumidification Capacity: 3 kg/h
  • Process Airflow: 600 m³/h
  • Dehumidification Wheel: 300 × 100 mm
  • Dimensions: 612 × 433 × 856 mm
  • Balanced Industrial Performance: Combines strong process and reactivation airflow.
  • Flexible Humidity Control: Adjustable 5%–95% RH range.

Working Principle

  • Air Intake & Filtration: Process and reactivation air pass through separate G4 filters for cleaner airflow.
  • Moisture Adsorption: The process fan forces humid air through the desiccant wheel, where moisture is adsorbed.
  • Dry Air Supply: Dehumidified air leaves the wheel through the process air outlet.
  • Wheel Regeneration: Heated reactivation air removes accumulated moisture from the desiccant wheel.
  • Moisture Exhaust: The reactivation fan discharges moisture-laden air outside.
  • Continuous Drying: Continuous wheel rotation enables simultaneous adsorption and regeneration.

MCH-600XF-01 Rotary Dehumidifier Working Principle

Product Parameters

Model Dehumidification Capacity (20°C, 60% RH) Test Conditions Power Supply Rated Power Rated Current
MCH-600XF-01 72 L/day 20°C, 60% RH 220V / 50Hz 4 kW 16 A
Process Airflow Reactivation Airflow Process Air External Static Pressure Reactivation Air External Static Pressure Process Air Duct Diameter Reactivation Air Duct Diameter
600 m³/h 200 m³/h 100 Pa 90 Pa Φ150 mm × 2 Φ100 mm × 2
Desiccant Rotor Size Filtration Device Operating Temperature Dimensions (L×W×H) Weight Humidity Setting Range
300 × 100 mm Primary Filter -10°C–50°C 612 × 433 × 856 mm 75 kg 5%–95% RH

Manufacturing & Quality Control

  • Base Material: SPCC cold-rolled steel sheet with clean, rust- and oil-free surfaces.
  • Welding Material: ER70S-6 welding wire for stable joint quality.
  • Weld Quality: Uniform welds, free from pores, slag inclusions, and cracks.
  • Flatness Control: Post-weld flatness maintained within ≤ 1 mm.
  • Surface Finish: Weld areas polished to Ra ≤ 3.2 μm.
  • Tolerance Control: GB/T 1804-m; post-weld length tolerance ±1 mm.
  • Protective Coating: 20–30 μm epoxy primer applied after welding.
  • Structural Strength: Strength test ≥ 350 MPa.
  • Assembly Accuracy: Component gap ≤ 0.5 mm; overall flatness ≤ 1.5 mm.

MCH-600XF-01 Rotary Dehumidifier Overall Assembly Dimensions

Circuit Diagram

MCH-600XF-01 Rotary Dehumidifier Circuit Diagram

Scroll to Top