Working Principle
Humid process air passes through the G4 filter and is driven through the desiccant wheel by the process fan, where moisture is adsorbed before dry air is discharged.
A separate regeneration air stream is filtered and heated before passing through the wheel to remove the absorbed moisture.
The regeneration fan exhausts the moisture-laden air, while the wheel rotates continuously to maintain stable dehumidification.

Product Parameters
| Model | Dehumidification Capacity (20°C, 60% RH) | Power Supply | Rated Power | Maximum Power | Rated Current |
| MCH-2000XF-01 | 312 L/day | 380V / 50Hz | 18 kW | 19 kW | 34 A |
| Process Airflow | Reactivation Airflow | Process Air External Static Pressure | Reactivation Air External Static Pressure | Process Air Duct Diameter | Reactivation Air Duct Diameter |
| 2100 m³/h | 780 m³/h | 380 Pa | 280 Pa | Φ250 mm × 2 | Φ150 mm × 1 |
| Desiccant Rotor Size | Filtration Device | Operating Temperature | Dimensions (L×W×H) | Weight | Humidity Setting Range |
| 570 × 200 mm | Primary Filter | -10°C–50°C | 920 × 683 × 1307 mm | 210 kg | 5%–95% RH |
Design & Manufacturing Quality
Large-Airflow Design
Ø250 mm process air and Ø150 mm reactivation air connections support industrial duct systems.
Smart Control
Humidity sensor, digital display, RS-485, mode switch, and status indicators simplify monitoring and integration.
Vertical Structure
The 920 × 683 × 1307 mm cabinet provides stable installation with integrated cooling.
Manufacturing Quality
ER70S-6 welding, Ra ≤ 3.2 μm surface finish, ≥ 350 MPa strength, and controlled dimensional tolerances ensure structural reliability.